Freestanding Tower Fan Coil Units

Vertical Exposed (HLC 34VE - 238VE) and Floor Standing High-Capacity (HLC-14LZ / HLC-20LZ) technical specifications and performance data

340 - 2,380 m3/h 1.8 - 12.6 kW Cooling 2.7 - 18.9 kW Heating From 37 dB(A)
PFAS-Free Water System 2-Pipe Changeover 270 mm Slim Profile Heating & Cooling Retrofit Ready iSAVE Compatible

iZONE Vertical Exposed & Floor Standing Fan Coil Units

Freestanding tower fan coil units for hydronic heating and cooling distribution. The HLC VE series offers 9 models in a slim 270 mm wide profile for standard rooms and retrofit installations. The HLC-LZ series provides high-capacity floor standing units for commercial applications requiring up to 15 kW of heating output.

All units connect to central iHEAT heat pumps or chillers via 2-pipe water circuits, delivering zone-controlled comfort without refrigerant in occupied spaces.

1. Vertical Exposed Fan Coil Units — Standard Series (HLC 34VE - 238VE)

9 models covering 340 to 2,380 m3/h airflow. Slim 270 mm wide freestanding tower design with front-facing air discharge. Suitable for offices, hotel rooms, residential living areas, retail spaces, and retrofit projects where ceiling installation is not practical.

Parameter HLC 34VE HLC 51VE HLC 68VE HLC 85VE HLC 102VE HLC 136VE HLC 170VE HLC 204VE HLC 238VE
Air Flow
High m3/h 3405106808501,0201,3601,7002,0402,380
Medium m3/h 2553835106387651,0201,2751,5301,785
Low m3/h 1702553404255106808501,0201,190
Cooling Capacity
Total Cooling W 1,8002,7003,6004,5005,4007,2009,00010,80012,600
Total Cooling BTU/h 6,1439,21512,28715,35918,43024,57430,71736,86043,004
Heating Capacity
Total Heating W 2,7004,0505,4006,7508,10010,80013,50016,20018,900
Total Heating BTU/h 9,21513,82318,43023,03827,64536,86046,07655,29164,506
Electrical
Power Input W 3752627696134152189228
Motor Power W 101620253020×225×230×240×2
Fan Motors qty 122223444
Acoustics
Noise Level dB(A) ≤37≤38≤40≤42≤44≤46≤48≤50≤52
Water Side
Water Supply kg/h 3244826558149361,2781,6021,9152,178
Water Resistance kPa 303030304040404050
Dimensions
Length mm 1,0001,0001,2001,3001,4001,6001,9002,1002,100
Width mm 270270270270270270270270270
Height mm 645645645645645645645645645

2. Floor Standing High-Capacity — HLC-LZ Series

High-capacity floor standing fan coil units for commercial lobbies, conference rooms, server rooms, and large open-plan spaces. 3HP and 5HP models with three-speed fan control.

Parameter HLC-14LZ (3HP) HLC-20LZ (5HP)
Cooling Capacity (W)
High7,40010,000
Medium5,9209,000
Low4,8107,000
Heating Capacity (W)
High11,10015,000
Medium8,88012,000
Low7,22010,000
Air Flow (m3/h)
High1,4002,000
Medium1,1001,740
Low8801,420
Electrical & Acoustics
Power Input W87176
Noise Level dB(A)≤50≤56
Water Side
Water Supply kg/h1,0102,000
Water Resistance kPa≤30≤33
Dimensions & Weight
Width mm480600
Depth mm230310
Height mm1,6801,895

Standard Test Conditions

Rated Capacity Conditions

  • Cooling: Chilled water inlet/outlet 7/12 °C, room air dry-bulb/wet-bulb 27/19.5 °C
  • Heating: Hot water inlet/outlet 60/50 °C, room air dry-bulb 20 °C
  • Noise: Measured at 1.5 m distance in semi-anechoic conditions, high fan speed
  • Water flow: Based on rated capacity at standard temperature differentials

High Static Pressure Configurations

For installations requiring ducted air distribution from the tower unit, high static pressure variants are available on the HLC 102VE and larger models. These configurations use upgraded fan assemblies to overcome duct resistance while maintaining rated airflow. Contact Karnot technical support for high static pressure model selection and duct design guidance.

Installation & Applications

Hotel Rooms & Suites

Slim 270 mm profile fits against walls or in alcoves. Quiet operation from 37 dB(A) ensures guest comfort. Individual zone control per room.

Offices & Meeting Rooms

Freestanding installation requires no ceiling work. Three-speed fan control adapts to occupancy. Models from 1.8 kW to 12.6 kW cover individual offices to open-plan floors.

Retail & Showrooms

Tower design complements interior layouts. HLC-LZ floor standing units deliver up to 15 kW heating for large ground-floor retail spaces with high ceilings.

Residential Retrofit

Replaces radiators with heating and cooling capability. No ceiling void required. Connects to iHEAT heat pump for a complete PFAS-free hydronic system.

Healthcare & Care Homes

Water-based distribution eliminates airborne refrigerant risk. Easy-access filters for hygiene maintenance. Quiet low-speed operation for patient areas.

Easy Retrofit Installation

No false ceiling required. Simple 2-pipe water connection. Electrical connection to standard supply. Floor-standing units can be operational within hours.

Capacity Selection Guide

Select the appropriate model based on calculated room cooling load. The figures below assume standard test conditions. For rooms with high solar gain, large glazing areas, or high occupancy, increase capacity by 15-25%.

Small Room / Office

15 - 25 m2
HLC 34VE or HLC 51VE
1.8 - 2.7 kW cooling

Medium Room / Suite

25 - 45 m2
HLC 68VE or HLC 85VE
3.6 - 4.5 kW cooling

Large Room / Open Plan

45 - 80 m2
HLC 102VE or HLC 136VE
5.4 - 7.2 kW cooling

Commercial / Lobby

80 - 150 m2
HLC 170VE - 238VE or HLC-LZ
9.0 - 15.0 kW cooling

All specifications are based on standard test conditions and are subject to change without notice. Actual performance may vary depending on installation conditions, water temperatures, and ambient environment. Contact Karnot Energy Solutions for project-specific sizing and selection assistance.

Karnot Energy Solutions Inc.Contact Us  |  iZONE Product Range  |  All iZONE Datasheets